FIRE TECHNOLOGY TO A HIGHER POWER

NFPA 286 Thermal Barrier Intumescent Coating

Part Number: F10E

FIRESHELL® (F10E) is a proprietary non-flammable, intumescing (expands up to 2000%) interior coating that provides oxygen starvation to fire. It is a non-toxic, water based, drain safe, no fuming GREEN product.

FIRESHELL® passes full scale room corner over foam NFPA 286 and E84 class A certified. It is a waterbased one part coating system that comes white but can be tinted different colors. This coating can be latex or oil based topcoated.

Applications:
  • For Walls, Foam, Attics, Crawl Spaces
  • Open cell insulation foam
  • Closed cell insulation foam
  • Bio foams

Approvals:
  • Meets NFPA 285 multi story Fire resistance over sprayfoam for ACM aluminum/sprayfoam commercial wall assemblies.
  • Meets IBC 803.2.1 over foam
  • Meets IBC 2603.9 over foam
  • Meets IRC 314.3 over foam
  • The first coating to pass NFPA 286 over Foam
  • Water based, 1-part, non-flammable, intumescing coating for interior use
  • E84 Cl 'A' verified
  • Meets Green Standards and Lead Paint Requirements
  • Meets EPA certification for Ultra Low VOC coating


You will need a Username & Password to view our certification materials.
Please CALL: 860.767.8772

ASTM E84 Test Reports

ASTM E84 PART # PRODUCT D.F.T. DESCRIPTION SUBSTRATE RESULTS
E84 F10E FIRESHELL®
Thermal Barrier
15 mils Standard test for surface burning characteristics of building materials Fiber cement board and select grade red oak flooring Flame:5 , Smoke:20


Miscellaneous Test Reports

MISCELLANEOUS PART # PRODUCT D.F.T. DESCRIPTION SUBSTRATE RESULTS
EPA Method 24 - VOC test F10E FIRESHELL® NA VOC test for LEED Compliance NA < 1g/l
Mold Resistance F10E FIRESHELL® NA ASTM D-3273-05 Resistance to growth of mold on the surface of interior coatings in an environmental chamber. ASTM D-3274-02 "Evaluating degree of surface disfigurement of paint film by fungal growth or soil and dirt accumulation Gypsum Wallboard No Mold Growth


NFPA 286 Test Reports

NFPA 286 PART # PRODUCT D.F.T. DESCRIPTION SUBSTRATE RESULTS
Full Scale Room Corner over CLOSED Cell Foam F10E FIRESHELL® 16 mils Specimen met the criteria set forth in the 2006 IBC Section 803.2.1 and conforms to IBC 2603.9 & IRC 314.3 on a 12' x 8' wood studded room with 4 1/2" of exposed closed cell foam FIRESHELL® Intumescent Coating over 4 1/2 inches of 2 pcf sprayfoam insulation No flame spread and no indication of excessive smoke
Full Scale Room Corner over OPEN Cell Foam F10E FIRESHELL® 14 mils Specimen met the criteria set forth in the 2006 IBC Section 803.2.1 and conforms to IBC 2603.9 & IRC 314.3 on a 12' x 8' wood studded room with 5 1/2" of exposed foam in the walls and 10" of exposed foam in the ceilings. FIRESHELL®Intumescent Coating over 5 1/2 inches & 10 inches of 1/2 pcf sprayfoam insulation Met the IBC acceptance criteria defined in IBC 803.2.1
Full Scale Room Corner over COMPOSITE FIBERGLASS over CLOSED Cell Foam F10E FIRESHELL® 15 mils Specimen met the criteria set forth in the 2006 IBC Section 803.2.1 and conforms to IBC 2603.9 & IRC 314.3 over a composite structure composite of fiberglass encasing 2lb foam. FIRESHELL® Intumescent Coating over 4 x 8 x2" thick composite fiberglass on foam wall panels attached together with bolts. No flame spread and no indication of excessive smoke
Full Scale Room Corner over OPEN Cell Foam F10E FIRESHELL® 13 mils Specimen met the criteria set forth in the 2006 IBC Section 803.2.1 and conforms to IBC 2603.9 & IRC 314.3 on a 12' x 8' wood studded room with 5 1/2" of exposed foam in the walls and 10" of exposed foam in the ceilings. FIRESHELL®Intumescent Coating over 6 inches wall & 10 inches ceiling of OPEN cell foam Met the IBC acceptance criteria defined in IBC 803.2.1


ICC AC377 approved Ignition Barriers Test Reports

ICC AC377 approved Ignition Barriers PART # PRODUCT D.F.T. DESCRIPTION SUBSTRATE RESULTS
NFPA 286 with Acc. Criteria AC377 appendix A on OPEN CELL FOAM CRAWL SPACES F10E FIRESHELL® 12 mils Flame spread and heat release using Full Scale Room Corner over Open Cell Foam 1/2# open cell foam (5 1/2" walls, 10" ceiling) with F10E compared to 1/4" plywood room superior to plywood, room meets AC377
NFPA 286 with Acc. Criteria AC377 appendix A on CLOSED CELL FOAM CRAWL SPACES F10E FIRESHELL® 14 mils Flame spread and heat release using Full Scale Room Corner over closed cell foam 2# closed cell foam(9" walls, 13" ceiling) with F10E compared to 1/4" plywood room superior to plywood, room meets AC377
NFPA 286 with Acc. Criteria AC377 appendix A BASELINE test NA NA NA BASELINE test: Flame spread and heat release using Full Scale Room Corner over Open Cell Foam Foam (7" walls, 11" ceiling) under 1/4" plywood room Plywood room fails at 4:29 min
Supplemental Product Data

Standard Colors for F10E & F1E
F10E Charcoal Black
Unacceptable Open Cell Surface Example
Coated Foam- What To Look For
FIRESHELL® In The News

Spray Foam Finally Gets a Price Competitive Edge Against Fiberglass Insulation and Batting

November 7, 2008 - Clinton, NJ - We in the sprayfoam insulation industry have battled, since the beginning, with upfront cost challenges of foam insulation versus fiberglass batting products.

We all have become experts at expounding on payback periods, the improvements in sound, air, mold, moisture, and structural rigidity that foam insulation provides. We've also become proficient at explaining inherent air conditioning, furnace, ducting and lumber cost reductions spray foam insulation allows. We have our payback calculators honed to a tee to help builders and owners see the true systems saving. Full Article


FIRESHELL® In The News

ICC-ES Approves New Fire Test Protocol for Spray Applied Polyurethane Foam in AC377

Birmingham, AL. June 3, 2009, the International Code Council Evaluation Service (ICC-ES) approved changes in AC-377, Acceptance Criteria for Spray Allied Polyurethane Foam. This approval had the effect of sun-setting a previous fire testing method and implementing a new one, with phaseout milestones extending to December 2010.

The new fire testing protocol, an NFPA 286 test modified for the purposes of testing alternative ignition barriers for SPF, becomes one of several available tests recognized within the AC-377. Full Article